Thông số kĩ Thuật:
Modello Model | Abbinamento compressore Compressor combination | Portata Flow-Rate | Caduta di pressione Pressure drop | Attacchi Connections | Alimentazione Power supply | Dimensioni [mm] Dimensions [mm] | Peso Weight | ||||
[l/min] | [m3/h] | [scfm] | [bar] | IN-OUT [ϕ] | [Ph/V/Fr] | A | B | C | [kg] | ||
AMD 3 | 3kW-4HP | 350 | 21 | 12 | 0.15 | G 3/8″ BSP-F | 1/230/50-60 | 310 | 345 | 435 | 21 |
AMD 6 | 4kW-5,5HP | 600 | 36 | 21 | 0.04 | G 1/2″ BSP-F | 1/230/50-60 | 370 | 515 | 475 | 25 |
AMD 9 | 5,5kW-7,5HP | 950 | 57 | 34 | 0.09 | G 1/2″ BSP-F | 1/230/50-60 | 370 | 515 | 475 | 26 |
AMD 12 | 7,5kW- 10HP | 1.200 | 72 | 42 | 0.14 | G 1/2″ BSP-F | 1/230/50-60 | 370 | 515 | 475 | 28 |
AMD 18 | 11kW- 15HP | 1.800 | 108 | 64 | 0.32 | G 1/2″ BSP-F | 1/230/50-60 | 370 | 515 | 475 | 32 |
AMD 25 | 15kW-20HP | 2.500 | 150 | 88 | 0.24 | G1″BSP-F | 1/230/50-60 | 345 | 420 | 740 | 34 |
AMD 32 | 18,5kW-25HP | 3.200 | 192 | 113 | 0.16 | G 1.1/4″ BSP-F | 1/230/50 | 345 | 445 | 740 | 39 |
AMD 43 | 22kW- 30 HP | 4.300 | 258 | 152 | 0.24 | G 1.1/4″ BSP-F | 1/230/50 | 345 | 445 | 740 | 40 |
AMD 52 | 22+kW-30+HP | 5.200 | 312 | 184 | 0.34 | G 1.1/4″ BSP-F | 1/230/50 | 485 | 455 | 825 | 49 |
AMD 61 | 30kW-40HP | 6.100 | 366 | 216 | 0.19 | G 1.1/2″ BSP-F | 1/230/50 | 555 | 580 | 885 | 54 |
AMD 75 | 37kW-50HP | 7.500 | 450 | 265 | 0.25 | G 1.1/2″ BSP-F | 1/230/50 | 555 | 580 | 885 | 56 |
AMD 105 | 55kW-75 HP | 10.500 | 630 | 371 | 0.14 | G 2″ BSP-F | 1/230/50 | 555 | 625 | 975 | 94 |
AMD 130 | 55+kW-75+HP | 13.000 | 780 | 459 | 0.20 | G 2″ BSP-F | 1/230/50 | 555 | 625 | 975 | 96 |
AMD 168 | 90kW-120 HP | 16.800 | 1.008 | 594 | 0.15 | G 2.1/2″ BSP-F | 1/230/50 | 665 | 725 | 1.105 | 144 |
AMD 190 | 90+kW-120+HP | 19.000 | 1.140 | 671 | 0,21 | G 2.1/2″ BSP-F | 3/400/50 | 645 | 920 | 1.100 | 189 |
AMD 220 | HOkW- 150HP | 22.000 | 1.320 | 777 | 0,28 | G 2.1/2″ BSP-F | 3/400/50 | 645 | 920 | 1.100 | 212 |
FATTORE DI CORREZIONE AL VARIARE DELLA PRESSIONE DI ESERCIZIO: / CORRECTION FACTOR FOR OPERATING PRESSURE CHANGES: | ||||||||
Pressione aria entrata / Intel air pressure barg | 4 | 5 | 6 | 7 | 8 | 10 | 12 | 14 |
Fattore/Factor | 0.77 | 0.86 | 0.93 | 1.00 | 1.05 | 1.14 | 1.21 | 1.27 |
FATTORE DI CORREZIONE AL VARIARE DELLA TEMPEMPERATURA AMBIENTE: / CORRECTION FACTOR FOR AMBIENT TEMPERATURE CHANGES: | |||||
Temperatura ambiente/Amb/ent temperature °C | < 25 | 30 | 35 | 40 | 45 |
Fattore/Factor | 1.00 | 0.95 | 0.88 | 0.79 | 0.68 |
FATTORE DI CORREZIONE AL VARIARE DELLA TEMPERATURA ARIA IN ENTRATA: / CORRECnON FACTOR FOR INLET AIR TEMPERATURE CHANGES: | ||||||
Temperatura aria/A/r temperature °C | <30 | 35 | 40 | 45 | 50 | 55 |
Fattore/Factor | 1.11 | 1.00 | 0.81 | 0.67 | 0.55 | 0.45 |
FATTORE DI CORREZIONE AL VARIARE DEL PUNTO DI RUGIADA (DEW POINT): / CORRECTION FACTOR FOR DEWPOINT CHANGES: | ||||
Punto di rugiada/Deiv Point °C | 3 | 5 | 7 | 10 |
Fattore/Factor | 0.91 | 1.00 | 1.10 | 1.26 |